Product Name : IT / IDC Power System
Description
Yuanguan specializes in the design and manufacture of UPS System and IT / IDC Power System. Please feel free to contact us if you want to know more about IT / IDC Power System. As a customer-oriented company, we are more than happy to provide detailed information for you.
Cloud room UPS system is available, special urgent UPS can be designed based on customers requirements.
I、Adapt PM Smart IDC Power System
Description:
Adapt PM Smart IDC Power System is a new generation uninterruptible power supply and integrated smart distribution anagement system developed by Emerson with its more than 40 years of experiences in large UPS production, advanced IDC power solutions and smart power management technologies.
Features:
- Both UPS and battery system use the aesthetics IT-style rack
- Embedded with the most delicate 30kVA rack-mounted UPS in the world with weight < 35kg and 3U height; Up to 5 UPS units can be paralleled inside one cabinet
- Embedded with hot swappable 150 kW bypass module
- Embedded with input/output distribution switch and manual maintenance bypass
- Embedded with Server Power Management System (SPM) to detect the switch status, voltage, current, PF, harmonics, and energy consumption of each branch circuit, and 2-level current pre-alarm settable
- Equipped with optional plug-and-play distribution module with 18 circuit breakers, so capacity can be expanded anytime and output distribution can be modified flexibly
- Equipped with optional ABB plug-and-play circuit breakers, the circuit breaker capacity expansion or load phase modulation can be realized without cutting the input power
- Both UPS power supply and load distribution can be configured dynamically. The UPS capacity and number of load circuits can be increased with the increase of user's IT systems
- Application scope:Medium IDCs of enterprises, medium-small IDCs in the fields of Finance, Security and Government…etc.
SPECIFICATION :
Model
Adapt PM150
Power (kVA/kW)
30, 60, 90, 120, 150
Dimension
Width x Depth x Height (mm)
600 x 1100 x 2000
Weight (kg)
450kg
Input specifications (rectifier)
Rated input voltage
380/400/415VAC,3-phase 4-wire
Rated operating frequency
50/60Hz
Input voltage range
228V~476V,-20%~+25% Full load,
linear derating at -25% - -40%; can take 70% load at -40%
Input frequency range
40Hz-70Hz
Input PF
Full load>0.99,Half load>0.98
Input current harmonic distortion (THDi)
<3%
Input power soft-start function
Yes, 5 ~ 30s settable
DC specifications
Output voltage regulation of charger
1%
Low DC ripple voltage
≦1%
Output specifications (inverter)
Inverter output voltage
380/400/415VAC,3-phase 4-wire
Output PF
1 (kW=kVA)
Voltage stability
Steady state
< ±1% Typical value
Transient state
< ±5% Typical value
Steady state response time
< 20 ms'
Inverter overload capability
110% 1 hour,125% 10 minutes,
150% 1 minute,>150% 200 ms.
Phase shift
With 100% balance load
<1°
With 100% imbalance load
<1°
Total harmonic
(THDv)
100% linear load
1%
100% nonlinear load
3%
Bypass
Bypass input voltage
380/400/415VAC,3-phase 4-wire
Bypass voltage range
Default value is -20%-+15%, -40%, -30%, -10% - +10%,
other ranges can be set via software
Bypass overload capability
135% general、170% 1 hour、1000% 100ms
System
Frequency
50Hz/60Hz (Settable)
Mains synchronization range
±2Hz(Default value),
adjustable with step of 0.5Hz within range of +/- 0.5Hz - 3Hz
Actual frequency precision (internal clock)
50Hz/60Hz ± 0.02%
System efficiency
>96% at load above 50%, >95% at load above 25%
SPM Smart Power Management System
Number of branch circuit breakers
18 ways X 3
Volume of branch circuit breakers
25A standard configuration, 10-63A optional
Monitoring functions
Status of mains input and branch circuit breakers, voltage, current,
PF, harmonics,energy consumption and 2-level current pre-alarm
Operating environmental
Operating temperature range
0~40℃ (See user manual for details)
Storage temperature
-25~70℃ (Without battery)
Relative humidity
0~95% No condensation
Altitude
not more than 1000m, derated by 1%
for every increase of 100m between 1000m and 2000m
Noise (1m)
55~62dB,Adjusted with load
Protection level
IP20(Internal dust filter)
Standard
Safety:IEC60950-1,IEC62040-1-1/ AS 62040-1-1,
EMC:IEC62040-2 / AS 62040-2/EN50091-2 CLASS A,
Design and test:IEC62040-3 / AS 62040-3
II、Chloride 80-NET
Features:
Chloride 80-NET features a transformer-free design with full IGBT double conversion technology allowing it to provide extraordinary savings on installation and running costs, while at the same time providing first class load protection.
Chloride 80-NET also features a full IGBT rectifier allowing for reductions in the size of gen sets, circuit protection, cabling and transformers.
III、NXr Series UPS
Features:
- On-Line Double Conversion, fully isolating the influences of power grid pollution and power failure from utility power supply and diesel generator to load
- Advanced DSP full digital control technologies realize higher system stability, online capacity expansion and maintenance
- Advanced distributed active parallel technology realizes parallel operation of 4 UPS units and online capacity expansion without centralized bypass cabinet
- Digital load sharing technology features extra low cross current and extreme high system reliability in parallel operation
- Adaptive to severe power grid environment due to extra wide input voltage and frequency ranges
- Extra strong capability to withstand output overload and short circuit, ensuring the system stability and system safety at limit conditions
- Intelligent battery management maintains battery automatically to prolong the battery life
- 6-inch extra large LCD that can display both Chinese and English, which is convenient to use
- Efficient heat dissipation and effective protection under severe environment due to its independent layer-sealed ventilation channel and redundant fan design, as well as the paint-protected circuit boards and built-in dust filter
- Applications:Medium IDCs of enterprises、Communication network operation centers、Medium-small IDCs…etc.
PECIFICATION:
POWER
30KVA
40KVA
60KVA
90KVA
100KVA
120KVA
160KVA
DEMINSION
Width×Depth× Height (mm)
600×843×1400
Weight (kg)
200
234
234
268
302
336
380
Input parameters (rectifier)
Rated input voltage
380/400/415VAC,3-phase 4-wire
Rated operating frequency
50/60Hz
Input voltage range
228V~476V,-20%~+25% Full load,
linear derating at -25% - -40%; can take 70% load at -40%
Input frequency range
40Hz~70Hz
Input power factor
Full load>0.99,Half load>0.98
Input harmonic current (THDi)
< 3%
Input soft start function
Yes, 5 – 30s settable
DC specifications
Output voltage regulation of charger
1%
Low DC ripple voltage
≤1%
Output specifications (inverter)
Inverter output voltage
380/400/415VAC,3-phase 4-wire
Output PF
0.9
Voltage stability
Steady state
< ±1% Typical value
Transient state
< ±5% Typical value
Steady state response time
< 20ms
Inverter overload capability
110% 1 hour, 125% 10 minutes, 150% 1 minute, >150% 200ms
Phase shift
With 100% balance load
< 1°
With 100% imbalance load
< 1°
Total harmonic (THDv)
100% linear load
1%
100% nonlinear load
3%
Bypass
Bypass input voltage
380/400/415VAC,3-phase 4-wire
Bypass voltage range
Default value is -20%-+15%, -40%, -30%, -10% - +10%,
+15%, other ranges can be set via software
Bypass overload capability
Long time operation at 135% rated load,
1 hour at 170% rated load, 1000% 100ms
System
Frequency
50Hz/60Hz(Settable)
Mains synchronization range
±2Hz(Default value),
adjustable with step of 0.5Hz within range of +/- 0.5Hz - 3Hz
Actual frequency precision (internal clock)
50Hz/60Hz±0.02%
System efficiency
>96% at load above 50%, >95% at load above 25%
Operating environmental
Operating temperature range
0~40℃(See user manual for details
Storage temperature
-25~70℃(Without battery)
Relative humidity
0~95%No condensation
Altitude
not more than 1000m, derated by 1%
for every increase of 100m between 1000m and 2000m
Noise (1m)
55~62dB,Adjusted with load
Protection level
IP20
Standard
Safety:IEC60950-1,IEC62040-1-1/ AS 62040-1-1,
EMC:IEC62040-2 / AS 62040-2/EN50091-2 CLASS A,
Design and test:IEC62040-3 / AS 62040-3
Cloud room UPS system is available, special urgent UPS can be designed based on customers requirements.
I、Adapt PM Smart IDC Power System
Description:
Adapt PM Smart IDC Power System is a new generation uninterruptible power supply and integrated smart distribution anagement system developed by Emerson with its more than 40 years of experiences in large UPS production, advanced IDC power solutions and smart power management technologies. Features:
|
SPECIFICATION :
Model | Adapt PM150 | ||
Power (kVA/kW) | 30, 60, 90, 120, 150 | ||
Dimension |
|||
Width x Depth x Height (mm) | 600 x 1100 x 2000 | ||
Weight (kg) | 450kg | ||
Input specifications (rectifier) | |||
Rated input voltage | 380/400/415VAC,3-phase 4-wire | ||
Rated operating frequency | 50/60Hz | ||
Input voltage range | 228V~476V,-20%~+25% Full load, linear derating at -25% - -40%; can take 70% load at -40% |
||
Input frequency range | 40Hz-70Hz | ||
Input PF | Full load>0.99,Half load>0.98 | ||
Input current harmonic distortion (THDi) | <3% | ||
Input power soft-start function | Yes, 5 ~ 30s settable | ||
DC specifications |
|||
Output voltage regulation of charger | 1% | ||
Low DC ripple voltage | ≦1% | ||
Output specifications (inverter) | |||
Inverter output voltage | 380/400/415VAC,3-phase 4-wire | ||
Output PF | 1 (kW=kVA) | ||
Voltage stability | Steady state | < ±1% Typical value | |
Transient state | < ±5% Typical value | ||
Steady state response time | < 20 ms' | ||
Inverter overload capability | 110% 1 hour,125% 10 minutes, 150% 1 minute,>150% 200 ms. |
||
Phase shift | With 100% balance load | <1° | |
With 100% imbalance load | <1° | ||
Total harmonic (THDv) |
100% linear load | 1% | |
100% nonlinear load | 3% | ||
Bypass |
|||
Bypass input voltage | 380/400/415VAC,3-phase 4-wire | ||
Bypass voltage range | Default value is -20%-+15%, -40%, -30%, -10% - +10%, other ranges can be set via software |
||
Bypass overload capability | 135% general、170% 1 hour、1000% 100ms | ||
System |
|||
Frequency | 50Hz/60Hz (Settable) | ||
Mains synchronization range | ±2Hz(Default value), adjustable with step of 0.5Hz within range of +/- 0.5Hz - 3Hz |
||
Actual frequency precision (internal clock) |
50Hz/60Hz ± 0.02% | ||
System efficiency | >96% at load above 50%, >95% at load above 25% | ||
SPM Smart Power Management System |
|||
Number of branch circuit breakers | 18 ways X 3 | ||
Volume of branch circuit breakers | 25A standard configuration, 10-63A optional | ||
Monitoring functions | Status of mains input and branch circuit breakers, voltage, current, PF, harmonics,energy consumption and 2-level current pre-alarm |
||
Operating environmental |
|||
Operating temperature range | 0~40℃ (See user manual for details) | ||
Storage temperature | -25~70℃ (Without battery) | ||
Relative humidity | 0~95% No condensation | ||
Altitude | not more than 1000m, derated by 1% for every increase of 100m between 1000m and 2000m |
||
Noise (1m) | 55~62dB,Adjusted with load | ||
Protection level | IP20(Internal dust filter) | ||
Standard | Safety:IEC60950-1,IEC62040-1-1/ AS 62040-1-1, EMC:IEC62040-2 / AS 62040-2/EN50091-2 CLASS A, Design and test:IEC62040-3 / AS 62040-3 |
II、Chloride 80-NET
Features:
Chloride 80-NET features a transformer-free design with full IGBT double conversion technology allowing it to provide extraordinary savings on installation and running costs, while at the same time providing first class load protection.
Chloride 80-NET also features a full IGBT rectifier allowing for reductions in the size of gen sets, circuit protection, cabling and transformers.
III、NXr Series UPS
Features:
|
PECIFICATION:
POWER | 30KVA | 40KVA | 60KVA | 90KVA | 100KVA | 120KVA | 160KVA | |
DEMINSION |
||||||||
Width×Depth× Height (mm) | 600×843×1400 | |||||||
Weight (kg) | 200 | 234 | 234 | 268 | 302 | 336 | 380 | |
Input parameters (rectifier) | ||||||||
Rated input voltage | 380/400/415VAC,3-phase 4-wire | |||||||
Rated operating frequency | 50/60Hz | |||||||
Input voltage range | 228V~476V,-20%~+25% Full load, linear derating at -25% - -40%; can take 70% load at -40% |
|||||||
Input frequency range | 40Hz~70Hz | |||||||
Input power factor | Full load>0.99,Half load>0.98 | |||||||
Input harmonic current (THDi) | < 3% | |||||||
Input soft start function | Yes, 5 – 30s settable | |||||||
DC specifications |
||||||||
Output voltage regulation of charger | 1% | |||||||
Low DC ripple voltage | ≤1% | |||||||
Output specifications (inverter) | ||||||||
Inverter output voltage | 380/400/415VAC,3-phase 4-wire | |||||||
Output PF | 0.9 | |||||||
Voltage stability | Steady state | < ±1% Typical value | ||||||
Transient state | < ±5% Typical value | |||||||
Steady state response time | < 20ms | |||||||
Inverter overload capability | 110% 1 hour, 125% 10 minutes, 150% 1 minute, >150% 200ms | |||||||
Phase shift | With 100% balance load | < 1° | ||||||
With 100% imbalance load | < 1° | |||||||
Total harmonic (THDv) | 100% linear load | 1% | ||||||
100% nonlinear load | 3% | |||||||
Bypass | ||||||||
Bypass input voltage | 380/400/415VAC,3-phase 4-wire | |||||||
Bypass voltage range | Default value is -20%-+15%, -40%, -30%, -10% - +10%, +15%, other ranges can be set via software |
|||||||
Bypass overload capability | Long time operation at 135% rated load, 1 hour at 170% rated load, 1000% 100ms |
|||||||
System |
||||||||
Frequency | 50Hz/60Hz(Settable) | |||||||
Mains synchronization range | ±2Hz(Default value), adjustable with step of 0.5Hz within range of +/- 0.5Hz - 3Hz |
|||||||
Actual frequency precision (internal clock) |
50Hz/60Hz±0.02% | |||||||
System efficiency | >96% at load above 50%, >95% at load above 25% | |||||||
Operating environmental |
||||||||
Operating temperature range | 0~40℃(See user manual for details | |||||||
Storage temperature | -25~70℃(Without battery) | |||||||
Relative humidity | 0~95%No condensation | |||||||
Altitude | not more than 1000m, derated by 1% for every increase of 100m between 1000m and 2000m |
|||||||
Noise (1m) | 55~62dB,Adjusted with load | |||||||
Protection level | IP20 | |||||||
Standard | Safety:IEC60950-1,IEC62040-1-1/ AS 62040-1-1, EMC:IEC62040-2 / AS 62040-2/EN50091-2 CLASS A, Design and test:IEC62040-3 / AS 62040-3 |